Lenovo 0U Basic Power Distribution Units (Withdrawn)

Product Guide (withdrawn product)

Home
Top
Author
Updated
1 Apr 2016
Form Number
TIPS0797
PDF size
9 pages, 205 KB

Abstract

The Lenovo zero-U (0U) Power Distribution Units (PDUs) are the ideal solutions when you need flexible, reliable, easy-to-deploy power distribution with branch circuit protection to minimize downtime. These rack-dense units distribute power to up to 24 outlets. The 0U Power Distribution Units are designed to be installed vertically in the rear channel of a Lenovo 42U rack, thereby not consuming any horizontal rack space that should be reserved for IT equipment (hence the term 0U).

Withdrawn from marketing: The PDUs listed in this product guide are withdrawn from marketing.

Introduction

The Lenovo zero-U (0U) Power Distribution Units (PDUs) are the ideal solutions when you need flexible, reliable, easy-to-deploy power distribution with branch circuit protection to minimize downtime. These rack-dense units distribute power to up to 24 outlets. The 0U Power Distribution Units are designed to be installed vertically in the rear channel of a Lenovo 42U rack, thereby not consuming any horizontal rack space that should be reserved for IT equipment (hence the term 0U).

Figure 1 shows the 0U 12 C19/12 C13 50A 3 Phase PDU installed in a Lenovo 42U rack. To the right is the 0U 24 C13 30A PDU.

0.378.jpg
Figure 1. Two of the available 0U Basic Power Distribution Units

Did you know?

With ever growing power densities in today’s rack environments, it is all too easy to add load in the wrong place and trigger an overload event. The 0U PDU offerings can minimize this impact, providing the ability to quickly recover with resettable circuit breakers for each designated bank of receptacles, referred to as load groups.

Introduction to PDUs

A power distribution unit (PDU) is a highly reliable, multiple outlet power strip, designed to consolidate line cords within the rack and distribute conditioned power from an uninterruptible power supply (UPS) or utility power to servers and other IT equipment. The PDU efficiently distributes power within the rack and provides fault-tolerant power redundancy for high availability requirements.

There are three types of PDUs available from Lenovo: basic, monitored, and switched and monitors. The PDUs covered in this document are of the basic type.

  • Basic: The simplest and most cost-effective power distribution. Available with various outlet configurations and line cord options to support differing systems and load requirements. The PDUs covered in this document are of this type.
  • Monitored (also known as PDU+): Provides the same benefits as a Basic PDU, but adds additional advanced PDU power monitoring down to the load group. This enables businesses to have a cross-platform rack level power and thermal view for trending analysis to improve power management.
  • Switched and monitored: These are advanced power management solutions, providing power monitoring at the outlet level, with increased accuracy at low amperages, for more precise views of power consumption down to the individual server level instead of at the consolidated load group. These PDUs also offer individual outlet switching (on/off), which allows for remote power sequencing and helps prevent unintended PDU overloading. Management can be performed by tools such as IBM Systems Director Active Energy Manager™.

Part number information

Table 1 lists the available 0U Basic PDUs.

Withdrawn from marketing: The PDUs listed in this product guide are withdrawn from marketing.

Table 1. Ordering part numbers and feature codes
Part number Feature code Description
46M4128 5924 0U 24 C13 30A PDU
46M4131 5925 0U 24 C13 32A PDU
46M4122 5922 0U 24 C13 16A 3 Phase PDU
46M4125 5923 0U 24 C13 30A 3 Phase PDU
46M4140 5926 0U 12 C19/12 C13 50A 3 Phase PDU
46M4143 5927 0U 12 C19/12 C13 32A 3 Phase PDU

The part numbers for the 0U Basic Power Distribution Units are included with the following items:

  • One power distribution unit
  • Mounting brackets for the following racks:
    • Two brackets for an S2 42U Standard Rack cabinet (Types 9307, 9956)
    • Two brackets for an Enterprise Rack cabinet (Types 1410, 9308)
  • Miscellaneous hardware kit (for attaching the mounting brackets to the PDU and installing the PDU in a rack cabinet)

Features

0U Basic PDUs have the following common features:

  • 0U rack-dense design with input cable connection, primary outlets, and breakers on one face to improve usability and cable management
  • Hardware included to mount in side pocket of rack
  • Easily accessible individual breakers per receptacle for high availability environments
  • Electronic over-current protection
  • High capacity up to 22 kW
  • Resettable UL489 rated circuit breakers

The use of PDUs simplifies cable management and increases accessibility. In addition, the button-mount design of these 0U Basic PDUs helps simplify deployment by providing tool-less rear mounting in 9360, 9361, and 9362 model rack cabinets, thereby reducing installation time.

Table 2 compares the power specifications of the 0U Basic PDUs.

Table 2. Specifications
Feature
0.7E9C.jpg
0U 24 C13 30A PDU 0U 24 C13 32A PDU 0U 24 C13 16A 3-phase PDU 0U 24 C13 30A 3-phase PDU 0U 12 C19/12 C13 50A 3-phase PDU 0U 12 C19/12 C13 32A 3-phase PDU
Part number 46M4128 46M4131 46M4122 46M4125 46M4140 46M4143
Feature code 5924 5925 5922 5923 5926 5927
Input power
Number of phases Single phase input Three phase input (wye)
Line cord Permanently attached line cord, 3 m length (9-ft, 10-in)
Line cord connector NEMA L6-30P IEC-309 P+N+Gnd IEC-309 3P+N+Gnd NEMA L21-30P CS8365L 3P+Gnd IEC-309 3P+N+Gnd
Plug design 0.90C6.gif 0.95E4.jpg 1.454.gif 0.A694.gif 0.ABFE.gif 1.454.gif
Input voltage 200-208V 220-240V 220-240V / 380-415V 200-208V 200-208V 220-240V / 380-415V
Input current rating 30A (24A in the USA) 32A 16A 30A (24A in the USA) 50A (40A in the USA) 32A
Maximum power rating 6240 VA 7680 VA 11040 VA 18720 VA 31200 VA 22920 VA
Output power
Number of C13 outlets 24 24 24 24 12 12
Number of C19 outlets 0 0 0 0 12 12
Output voltage rating 200-208V 220-240V 220-240V 200-208V 200-208V 220-240V
Output current rating Each outlet: 10 amps (VDE) / 15 amps (UL/CSA) Each C13 outlet: 10 amps (VDE) / 15 amps (UL/CSA)
Each C19 outlet: 16 amps (VDE) / 20 amps (UL/CSA)
Number of phases Single phase output
Circuit breakers Three double-pole branch rated circuit breakers rated at 20A Six double-pole branch rated circuit breakers rated at 20A
Number of load groups 3 3 3 3 3 3
Mechanical and environment
Physical dimensions DxWxH 3.35 x 1.75 x 35.4 in / 85 x 44 x 900 mm 3.35 x 1.75 x 47.2 in / 85 x 44 x 1200 mm
Weight 3.8 kg / 8.4 lb 4.5 kg / 9.9 lb 3.8 kg / 8.4 lb 3.7 kg / 8.2 lb 7.7 kg / 17 lb 5.9 kg / 13 lb
Operating temperature 10°C to 55°C (50°F to 122°F)
Operating humidity 5% - 90% (noncondensing)

Connectors

The 0U Basic PDUs with only C13 connectors have the components and controls shown in Figure 2.

1.2E42.jpg
Figure 2. 0U Basic PDUs with C13 connectors

The 0U Basic PDUs with C13 and C19 connectors have the components and controls shown in Figure 3.

3.49AC.jpg
Figure 3. 0U Basic PDUs with C13 and C19 connectors

A close-up of the circuit breakers of the two types of PDUs is shown in Figure 4.

4.4BCA.jpg
Figure 4. Circuit breakers of the 24 C13 PDU and 12 C19 / 12 C13 PDU

As Figure 4 shows, the PDUs with C13 connectors have three double-pole branch-rated circuit breakers, each rated at 20A. Each circuit breaker is a load group and is associated with eight C13 outlets. The PDUs with C13 and C19 connectors have six double-pole branch-rated circuit breakers each rated at 20A. Each pair of circuit breakers is a load group and is associated with eight C13 outlets.

Warranty

The 0U Basic PDUs are offered with a three-year limited warranty.

Supported rack cabinets

The 0U Basic PDUs can be installed in the following racks:

  • S2 42U Standard Rack cabinet (Types 9307, 9956)
  • Enterprise Rack cabinet (Types 1410, 9308)
  • 42U 1200mm Deep Dynamic Rack (Type 9360)
  • 42U 1200mm Deep Static Rack (Type 9361)
  • 47U 1200mm Deep Static Rack (Type 9362)

Note: When the 0U PDUs are installed in 1000mm racks such as the S2 42U Standard Rack cabinet, cable management arms (CMAs) cannot be used in the mounted servers.

The PDUs are installed vertically in side pockets of the rack. The Deep Dynamic and Deep Static racks support the button-mount design of the PDU and do not require additional hardware. Installation is shown in Figure 5. For the S2 42U Standard Rack and Enterprise Rack, the PDU part numbers include the necessary mounting hardware.

6.46C8.jpg
Figure 5. Installing the 0U Basic PDU in a Deep Dynamic or Deep Static rack

Related product families

Product families related to this document are the following: