Author
Updated
9 Dec 2024Form Number
LP1723PDF size
15 pages, 554 KBAbstract
The RT11kVA 6U Rack or Tower Uninterruptible Power Supply-G2 offerings provide extended power protection with increased efficiency and simplified power management to safeguard high-availability of Lenovo server environments. With efficiency ratings of up to 98%, these compact 6U rack or tower designs can help reduce energy usage without compromising performance or reliability.
The 6U Rack or Tower UPS-G2 units can be installed in a data center rack cabinet or can be used as tower UPS units in office and distributed IT environments where extended power protection is required.
Change History
Changes in the December 9, 2024 update:
- The following is withdrawn from marketing under Technical specifications section
- UPS Network Management Card-G2, 4C57A87624
Introduction
The RT11kVA 6U Rack or Tower Uninterruptible Power Supply-G2 offerings provide extended power protection with increased efficiency and simplified power management to safeguard high-availability of Lenovo server environments. With efficiency ratings of up to 98%, these compact 6U rack or tower designs can help reduce energy usage without compromising performance or reliability.
The 6U Rack or Tower UPS-G2 units can be installed in a data center rack cabinet or can be used as tower UPS units in office and distributed IT environments where extended power protection is required.
The 6U Rack UPS-G2 unit (RT11kVA) is shown in Figure 1
Figure 1. RT11kVA 6U Rack UPS-G2 unit (Power module (top) and Battery module (bottom))
Did you know?
6U Rack or Tower UPS-G2 units feature Advanced Battery Management (ABM) technology that uses a unique three-stage charging technique that significantly extends battery service life and optimizes recharge time, compared to traditional charging methods.
6U Rack or Tower UPS-G2 units come standard with the Maintenance Bypass module, which enhances system availability by providing service continuity during UPS maintenance and upgrades.
6U Rack or Tower UPS-G2 units come standard with UPS Manager software that integrates seamlessly with the major virtualization platforms, which enables you to view and manage your entire power system from your current dashboard. It also triggers live migration during power outages and avoids data loss by gracefully shutting down virtual machines and hosts in a cluster if there is an extended power outage.
Ordering information
The following tables show the orderable feature code, CTO, LFO and part number codes for the 6U Rack or Tower UPS-G2 models and options.
Tip: Eaton is the vendor for listed models.
Table 1. Ordering feature code, CTO and LFO model
Description | Feature code | CTO | LFO |
UPS unit | |||
IBM RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC) | BV3E | 7DD5CTO4WW | 7DD5A00AWW |
Extended Battery Modules (EBM) | |||
8kVA/11kVA 3U Rack or Tower Extended Battery Module-G2 | BV3F | 7DD5CTO4WW | 7DD5A00BWW |
Table 2. Ordering feature code and Part number option
Description | Feature code | Part number |
Environmental Monitoring Probe-G2 | BV3H | 4XF7A87625 |
- The RT11kVA 6U Rack or Tower UPS-G2 model ships standard with the Network Management Card (NMC) which includes software license for IPM.
The RT11kVA 6U Rack or Tower UPS-G2 model includes the following items:
- A power module
- A battery module
- A Maintenance Bypass module (MBP) with the hardwired MBP detection cable and two hardwired power cables for connections to the power module's terminal block
- An accessory kit that contains the following items:
- Power Module
- Extended battery module (EBM)
- Network Management Card
- (2) brackets for 19’ mounting
- (2) Rack-mounting kit
- Serial cable
- USB cable
- (2) Supports for tower mounting
- Link plate
- Safety instructions
- Quickstart guide
The Extended Battery Modules are shipped with the following items:
- An accessory kit that contains the following items:
- Rack-mount kit
- Tower kit
- EBM power cable
- EBM detection cable
- Documentation package
The RT11kVA 6U Rack or Tower UPS-G2 units have a hardwired terminal block connector for AC input power.
- All 6U Rack or Tower UPS-G2 models come standard with a NMC included with the models.
Network Management Card (NMC)
The NMC provides convenient, over-the-network UPS remote monitoring and management through a standard web browser ( IPM software ).
Figure below shows the UPS NMC.
Figure 2. UPS Network Management Card
The NMC includes the following features:
- Versatile connectivity through HTTP, SNMP, SMTP, Telnet, SSL, and SSH
- Simultaneous shutdown of protected servers
- Configuration of automatic email messages in response to UPS alarms and to transmit reports
- Customizable actions, including automatic shutdown if there is an extended power failure with standard UPS Power Protector software
- Control of UPS on/off switching with a web browser
- Adjustment and control of load segments through the HTML interface, including sequential starting of the installation and optimization of backup time by shutting down non-priority systems
- Automatic date and time adjustment through an NTP server
- Dual stack IP v4/IP v6
- Recording of events and measurements in the card log
- Data and event logging in the nonvolatile memory
- Card firmware update through the network
- 10/100 Mb Ethernet (RJ-45 connector) with auto-negotiation
- Measurement of humidity and temperature with the Environmental Monitoring Probe (EMP)
- Includes IPM software
Environmental Monitoring Probe (EMP)
EMP (part number 4XF7A87625) is used to report local temperature and humidity values and make that information available to management tools. The EMP connects to the UPS via the NMC. The EMP is shown below.
Figure 3. Environmental Monitoring Probe
The Environmental Monitoring Probe has the following features:
- Monitors temperature, humidity, and status of two user-provided contact devices or sensors
- Connects to an NMC through an RJ-45 CAT5 Ethernet cable (1 m cable that is included with the EMP)
- Can be located up to 20 m (65.6 ft) from the UPS
- Measures ambient temperatures between 0 - 80 °C (32 - 176 °F), with an accuracy of ±1 °C (33.8° F)
- Measures relative humidity between 10 - 90%, with an accuracy of ±5%
- Displays temperature, humidity, and contact closure status through a Web browser
- Supports user-defined alarm thresholds for temperature, humidity, and contact closure status
- Stores events in the NMC's event log
- Sends SNMP alarms to network management systems
- Sends email notifications through SMTP
Note: The EMP requires Network Management Card ( NMC )
Features
A UPS is a device that acts as a defensive barrier between electronic equipment and incoming power problems. It conditions, regulates, and filters out power disturbances to ensure a clean power source for IT equipment. A UPS also provides battery backup if there is a power failure.
In today’s high availability server environments, unplanned power outages or line quality irregularities can have a considerable financial impact on all sized businesses. The typical utility power is 99.9% available, but that means that there can be almost 9 hours of downtime a year, not to mention brownouts and other power quality problems. Selecting the right UPS can help protect against these potentially costly issues.
The RT11kVA 6U Rack or Tower UPS-G2 units protect against the following power problems: power failures, power sags, power surges, under-voltage, electrical line noise, over-voltage, frequency variation, switching transients, and harmonic distortion.
The RT11kVA 6U Rack or Tower UPS-G2 models offer the following features:
- High-efficiency protection delivers more real power (Watts) in a compact tower or 6U rack design, which lowers power and cooling consumption
- Graphical Liquid Crystal Display (LCD) provides intuitive configuration, management, and monitoring capabilities in the following languages to reduce management complexity:
- English
- French
- German
- Spanish
- Russian
- Portuguese
- Italian
- Hot-swappable batteries for maximum uptime, availability, and ease of maintenance
- Standard UPS Power Manager software provides effective local or remote power monitoring and management for servers and virtual machines, and allows for graceful remote system shutdown
- ABM technology significantly extends battery service life and optimizes recharge time
- Optional external battery modules (EBMs) provide extra run time to critical systems during a prolonged power outage
- Standard NMC provides enhanced UPS monitoring and control over-the-network through a standard web browser
- Environmental Monitoring Probe provides thermal management requirements (temperature and humidity)
- Standard Maintenance Bypass enhances availability by providing service continuity during UPS maintenance and upgrades
- Provides dual channel communication through the USB or RS-232 port and an NMC at the same time to maximize communications flexibility
- Flash upgrades firmware for both the UPS and the NMC, which makes it an ideal solution for remote locations
- Includes ROO and RPO connectors to control power of the UPS unit through a wired remote switch
Technical specifications
The following table lists the technical specifications for the 11kVA 6U Rack or Tower UPS-G2 models.
* G2 NMC M2 4C57A87624, G3 NMC M3 4C57A97269
Note: Lenovo no longer offers the IPM software with the M3 NMC and any 7DD5 UPS units pre-installed with an M3 NMC. An IPM license can be purchased through an Eaton authorised partner. To find the nearest Eaton partner, connect to the following URL, fill in the form and select your country from the Country drop-down list. The US web link allows selecting any other country.
Following table lists the expected period that the 6U Rack or Tower UPS-G2 models operates only on batteries, depending on the load.
Note: Battery backup times are approximate and can vary with equipment, configuration, battery age, and temperature.
Connectors and controls
The 6U Rack or Tower UPS-G2 units have a 5-button graphical LCD on the front. It provides useful information about the UPS itself, load status, events, measurements, and settings.
Figure 4 shows the control panel on the front of the 6U Rack or Tower UPS-G2.
Figure 4. Control panel on the front of the 6U Rack or Tower UPS-G2
The following functions are available on the control panel:
- Status information: Displays the battery status, load percentage, output power, operational mode, and load group information.
- Measurements: Displays the output Watts/VA, amperage, power factor, voltage, frequency, input voltage, input frequency, battery voltage, efficiency, and power usage.
- Control: Displays the battery test, reset error state, configure load segments, clear power usage measurements, and restore settings.
- Settings: Allows you to change product general parameters and set input and output parameters, on/off conditions, and battery configuration.
- Event log: Displays the stored events, selects faults, alarms and events to display, and clears events.
- Fault log: Displays the event log and alarm history.
- Identification: Displays the machine type, model, and serial number of the unit, and the firmware level of the UPS, including the NMC’s firmware level and IP address.
Figure below shows the rear view of the RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC)
Figure 5. Rear view of the RT11kVA 6U Rack or Tower UPS-G2 (200-240VAC)
Figure below shows the rear view of the 11kVA 3U Rack or Tower Extended Battery Module-G2
Figure 6. Rear view of the 11kVA 3U Rack or Tower Extended Battery Module-G2
Physical specifications
The RT11kVA 6U Rack or Tower UPS-G2 Power Module has the following physical specifications (approximate):
- Height: 260 mm (10.2 in.)
- Width: 440 mm (17.3 in.)
- Depth: 700 mm (27.6 in.)
- Weight:
- 11kVA 86 kg (189.6 lb)
The 11kVA 3U Rack or Tower Extended Battery Module has the following physical specifications (approximate):
- Height: 440 mm (17.3 in.)
- Width: 680 mm (26.8 in.)
- Depth: 130 mm (5.1 in.)
- Weight: 65 kg (143 lb)
Operating environment
The RT11kVA 6U Rack or Tower UPS-G2 unit is supported in the following environments:
- Temperature (operation): 0 - 40 °C (32 - 104 °F), with linear derating for altitude
- Relative humidity: 0 - 95%
- Maximum altitude (operation): 3,000 m (9,843 ft)
Agency approvals
The RT11kVA 6U Rack or Tower UPS-G2 units conform to the following regulations:
- RoHS Compliant
- BESC
- CBSA
- CE
- cUL/CSA
- Pvoc
- SGS
- UKCA
- UL
Warranty
The 11kVA 6U Rack or Tower UPS-G2 models and the Extended Battery Module (EBM), including batteries, have a 3-year warranty, 9x5 Next Business Day (NBD) onsite response for hardware only. Software is owned by Eaton.
Management software
Eaton’s Intelligent Power Manager (IPM) software for disaster avoidance applications provides the tools you need to monitor and manage power equipment in physical or virtual environments to keep IT devices running during a power or environmental event. This innovative software ensures system uptime and data integrity by allowing you to remotely monitor, manage and control devices on your network. IPM provides a solution that is easy to use, maintains business continuity and allows you to do more with less.
Intelligent Power Manager (IPM)
IPM is an easy-to-use disaster avoidance platform with sophisticated capabilities that include triggering alerts and automating resolutions to keep applications running. IPM enables you to:
- Leverage Eaton’s integrations with industry leaders to keep critical applications running and automate resolutions for your entire network risking potential downtime.
- Migrate workloads to increase system uptime and minimize generator load by suspending non-critical virtual machines.
- Power cap servers to keep critical loads running longer by limiting server power consumption.
- Support for 5 nodes.
The Intelligent Power Manager (IPM) offers three levels of licenses
Monitor, manage and optimize. IPM Optimize is the premium offering and provides the most complete set of capabilities.
Maintain business continuity: Minimize operating expenses
- Intelligent load-shedding: Increase system uptime while extending battery runtime and minimizing generator load by suspending non-critical virtual machines.
- Site Recovery Manager failover: Reduce data recovery expenses by syncing primary and disaster-recovery sites prior to power failures.
- Power capping on demand: Keep critical workloads running longer during a power outage by limiting server power consumption.
Eaton’s Intelligent Power Manager resources:
Refer to the following resources:
Eaton’s software subscription
Intelligent Power Manager software subscription for eligible Lenovo UPS-G2 models include a 3-year subscription for up to 5 equipment nodes of Eaton’s Intelligence Power Manager (IPM) software (Optimize subscription).
IPM subscription is available from:
Note:
To use the IPM software, you must have the NMC installed.
UPSes, PDUs and ATSs, as well as rack mounted servers, hypervisors, and storage devices count as nodes.
Supported servers
The RT11kVA 6U Rack or Tower UPS-G2 offerings are compatible with all ThinkSystem, System x and ThinkServer systems and other devices that require AC power.
To determine the best fit UPS for a particular configuration, the following needs to be considered:
- Total power load of the hardware that will be connected to the UPS
- Number and type of outlets required
- UPS outlet and group limitations for connecting the hardware to the UPS
To help calculate the power consumption and current value in different deployments, use the Lenovo Capacity Planner (LCP). The tool can be leveraged online from https://datacentersupport.lenovo.com/us/en/solutions/lnvo-lcp
The Lenovo Capacity Planner (LCP) is a useful tool to determine the power draw of other devices such as storage and switching that will be attached to the UPS, refer to the products user manual for the maximum power draw.
Supported rack cabinets
The RT11kVA 6U Rack or Tower UPS-G2 units can be installed in all 19 inch rack cabinets.
- For specifications about these racks, see the Lenovo Rack Cabinet Reference, available from:
https://lenovopress.com/lp1287-lenovo-rack-cabinet-reference
Related publications and links
For more information about this topic, see the following resources:
- Product specifications and resources - RT11kVA 6U UPS-G2 (200-240VAC):
- Network Management Card
- Lenovo Rack Cabinet Reference
- Lenovo Capacity Planner (LCP):
Trademarks
Lenovo and the Lenovo logo are trademarks or registered trademarks of Lenovo in the United States, other countries, or both. A current list of Lenovo trademarks is available on the Web at https://www.lenovo.com/us/en/legal/copytrade/.
The following terms are trademarks of Lenovo in the United States, other countries, or both:
Lenovo®
System x®
ThinkServer®
ThinkSystem®
Other company, product, or service names may be trademarks or service marks of others.
Configure and Buy
Full Change History
Changes in the December 9, 2024 update:
- The following is withdrawn from marketing under Technical specifications section
- UPS Network Management Card-G2, 4C57A87624
Changes in the November 20, 2024 update:
- Updated details for the note under Technical specifications section
- Lenovo no longer offers software with M3 NMC
Changes in the October 7, 2024 update:
- Added the following note under Technical specifications section
- Lenovo no longer offers software with M3 NMC
Changes in the September 3, 2024 update:
- Added the following option under Technical specifications section
- UPS Gigabit Network Management Card-G3 (G3 NMC M3), 4C57A97269
Changes in the August 6, 2024 update:
- Updated the warranty statement under Warranty section
Changes in the July 17, 2024 update:
- Updated the following rack cabinet URL under- Supported rack cabinets section
- https://lenovopress.lenovo.com/lp1287-lenovo-rack-cabinet-reference#availability=Available
Changes in the August 10, 2023 update:
- Updated URLs - Related publications and links section
Changes in the June 22, 2023 update:
- Updated Warranty and support - Warranty section
First published: May 25, 2023
Course Detail
Employees Only Content
The content in this document with a is only visible to employees who are logged in. Logon using your Lenovo ITcode and password via Lenovo single-signon (SSO).
The author of the document has determined that this content is classified as Lenovo Internal and should not be normally be made available to people who are not employees or contractors. This includes partners, customers, and competitors. The reasons may vary and you should reach out to the authors of the document for clarification, if needed. Be cautious about sharing this content with others as it may contain sensitive information.
Any visitor to the Lenovo Press web site who is not logged on will not be able to see this employee-only content. This content is excluded from search engine indexes and will not appear in any search results.
For all users, including logged-in employees, this employee-only content does not appear in the PDF version of this document.
This functionality is cookie based. The web site will normally remember your login state between browser sessions, however, if you clear cookies at the end of a session or work in an Incognito/Private browser window, then you will need to log in each time.
If you have any questions about this feature of the Lenovo Press web, please email David Watts at dwatts@lenovo.com.