RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower Uninterruptible Power Supplies

Product Guide (withdrawn product)

Home
Top
Updated
6 Mar 2024
Form Number
TIPS1231
PDF size
23 pages, 1.0 MB

Abstract

The RT1.5kVA, RT2.2kVA, and RT3kVA 2U Rack or Tower Uninterruptible Power Supply (UPS) offerings provide extended power protection with increased efficiency and simplified power management to safeguard the high-availability of Lenovo server environments. With efficiency ratings of up to 99%, these compact 2U rack or tower designs can help reduce energy usage without compromising performance or reliability.

Change History

Changes in the March 6, 2024 update:

  • The following UPS models are withdrawn:
    • RT1.5kVA 2U Rack or Tower UPS (100-125VAC), 55941AX
    • RT2.2kVA 2U Rack or Tower UPS (100-125VAC), 55942AX
    • RT2.2kVA 2U Rack or Tower UPS (200-240VAC), 55942KX
    • RT3kVA 2U Rack or Tower UPS (100-125VAC), 55943AX
    • RT3kVA 2U Rack or Tower UPS (200-240VAC), 55943KX
    • 1.5kVA/2.2kVA 2U Rack or Tower Extended Battery Module, 55942BX
    • 3kVA 2U Rack or Tower Extended Battery Module, 55943BX

Introduction

The RT1.5kVA, RT2.2kVA, and RT3kVA 2U Rack or Tower Uninterruptible Power Supply (UPS) offerings provide extended power protection with increased efficiency and simplified power management to safeguard the high-availability of Lenovo server environments. With efficiency ratings of up to 99%, these compact 2U rack or tower designs can help reduce energy usage without compromising performance or reliability.

The 2U Rack or Tower UPS units can be installed in a data center rack cabinet or can be used as tower UPS units in office and distributed IT environments where extended power protection is required.

The 2U Rack UPS unit with the Extended Battery Module is shown in Figure 1.

0.10B2.gif
Figure 1. 2U Rack UPS unit (top) with Extended Battery Module (bottom)

Did you know?

2U Rack or Tower UPS units feature Advanced Battery Management (ABM) technology that uses a unique, three-stage charging technique that significantly extends battery service life and optimizes recharge time compared to traditional charging methods.

2U Rack or Tower UPS units can enhance system availability with individual receptacle groups or load segments that can be programmed and controlled, which allows mission-critical devices to be prioritized during shutdown to preserve battery run time if there is a prolonged power outage.

2U Rack or Tower UPS units come standard with UPS Power Manager software that integrates seamlessly with the major virtualization platforms, which enables you to view and manage your entire power system from your current dashboard. It also triggers live migration during power outages and avoids data loss by gracefully shutting down virtual machines and hosts in a cluster if there is an extended power outage.

Ordering information

Table 1 shows the orderable part numbers and feature codes for the 2U Rack or Tower UPS models and options.

Table 1. Ordering part numbers and feature codes

Part number Feature code Description
UPS units
55941AX A53S (5594-RU1) RT1.5kVA 2U Rack or Tower UPS (100-125VAC)
55941KX A53T (5594-RU1) RT1.5kVA 2U Rack or Tower UPS (200-240VAC)
55942AX A53U (5594-RU2) RT2.2kVA 2U Rack or Tower UPS (100-125VAC)
55942KX A53V (5594-RU2) RT2.2kVA 2U Rack or Tower UPS (200-240VAC)
55943AX A53W (5594-RU3) RT3kVA 2U Rack or Tower UPS (100-125VAC)
55943KX A53X (5594-RU3) RT3kVA 2U Rack or Tower UPS (200-240VAC)*
Extended Battery Modules (EBMs)
55942BX A53Y 1.5kVA/2.2kVA 2U Rack or Tower Extended Battery Module
55943BX A53Z 3kVA 2U Rack or Tower Extended Battery Module
Options
46M4110 6145 UPS Network Management Card*
46M4113 6146 Environmental Monitoring Probe

* RT3kVA 2U Rack or Tower UPS (200-240VAC) comes standard with the UPS Network Management Card included in the box.

Note: listed units above, are not entitled to a free 3-year IPM license.

The UPS models are shipped with the following items:

  • An accessory kit that contains the following items:
    • Rack-mount kit
    • Rack installation instructions
    • Tower kit
    • Serial cable: 1.2 m (4 ft)
    • USB cable
    • Remote On/Off (ROO) and Remote Power Off (RPO) connector
  • Documentation package
  • Software CD, which contains UPS Manager power management software

The Extended Battery Modules are shipped with the following items:

  • An accessory kit that contains the following items:
    • Rack-mount kit
    • Tower kit
    • EBM power cable
    • EBM detection cable

The 100-125 V UPS models ship with the following fixed line cords:

  • RT1.5kVA 2U Rack or Tower UPS (100-125VAC): 2.5 m (8 ft) line cord with NEMA 5-15P plug
  • RT2.2kVA 2U Rack or Tower UPS (100-125VAC): 2.5 m (8 ft) line cord with NEMA 5-20P plug
  • RT3kVA 2U Rack or Tower UPS (100-125VAC): 2.5 m (8 ft) line cord with NEMA L5-30P plug

The RT1.5kVA, RT2.2.kVA, and RT3kVA 200-240 V UPS models do not ship with line cords. Table 2 and Table 3 list the compatible line cords which are suitable for RT1.5kVA and RT2.2kVA/RT3kVA 200-240 V UPS models, respectively.

Table 2. Line cords for 200-240 V units (RT1.5kVA models)

Description Part number Feature code
Argentina 10A/250V C13/ IRAM 2073 4.3m line cord 81Y2384 6492
Australia 10A/250V C13/ AS/NZS 3112/2000 4.3m line cord 81Y2383 6574
Brazil 10A/250V C13/ NBR 14136 4.3m line cord 81Y2387 6404
China 10A/250V C13 / GB2099.1 4.3m line cord 81Y2378 6580
Denmark 10A/250V C13/SB107-2-DI 4.3m line cord 81Y2382 6575
Europe 10A/250V C13 / CEE 7/7 4.3m line cord 81Y2376 6572
India 10A/250V C13/IS 6538 4.3m line cord 81Y2386 6567
Israel 10A/250V C13/ SI 32 4.3m line cord 81Y2381 6579
Italy 10A/250V C13/ CEI 23-16 4.3m line cord 81Y2380 6493
Korea 12A/250V C13/KSC 8305 4.3m line cord 81Y2385 6494
South Africa 10A/250V C13/ SANS 164-1 4.3m line cord 81Y2379 6576
Switzerland 10A/250V C13/SEV 1011 4.3m line cord 81Y2390 6578
Taiwan 10A/250V C13/CNS 10917 4.3m line cord 81Y2389 6531
United Kingdom 10A/250V C13 / BS 1363A 4.3m line cord 81Y2377 6577

Table 3. Line cords for 200-240 V units (RT2.2kVA/RT3kVA models)

Description Part number Feature code
C19 4.3m cord - NEMA L6-20P 40K9772 6275
C19 4.3 meter Line Cord - UK 40K9767 6278
C19 4.3 meter Line Cord - Europe 40K9766 6279
C19 4.3 meter Line Cord - S Africa 40K9770 6280
C19 4.3 meter Line Cord - Italy 40K9768 6281
C19 4.3 meter Line Cord - Israel 40K9771 6282
C19 4.3 meter Line Cord - Dmk/Swiss 40K9769 6283
C19 4.3 meter Line Cord - Australia/NZ 40K9773 6284
C19 4.3 meter Line Cord - India 40K9776 6285
Taiwan 16A/250V C19/CNS 10917 4.3m line cord 90Y3035 6287
C19 4.3 meter Line Cord - China 40K9774 6288
South Korea 15A/250V C19/KSC 8305 4.3m line cord 90Y3034 6289
Japan 15A/200V C19/JIS C-8303 4.3m line cord 41Y9233 6291
C19 4.3 meter Line Cord - Argentina 40K9777 6276
C19 4.3 meter Line Cord - Brazil 40K9775 6277

All 2U Rack or Tower UPS models except model 3KX come equipped with a communication bay for the installation of an optional Network Management Card (46M4110). Model 3KX ships standard with a Network Management Card (NMC) in the box.

The NMC provides convenient, over-the-network UPS remote monitoring and management through a standard web browser or UPS Power Manager software. Figure 2 shows the UPS NMC.

UPS Network Management Card
Figure 2. UPS Network Management Card

The NMC has the following features:

  • Versatile connectivity through HTTP, SNMP, SMTP, Telnet, SSL, and SSH
  • Simultaneous shutdown of protected servers
  • Configuration of automatic email messages in response to UPS alarms and to transmit reports
  • Customizable actions, including automatic shutdown if there is an extended power failure with standard UPS Power Protector software
  • Control of UPS on/off switching with a web browser
  • Adjustment and control of load segments through the HTML interface, including sequential starting of the installation and optimization of backup time by shutting down non-priority systems
  • Automatic date and time adjustment through an NTP server
  • Dual stack IP v4/IP v6
  • Recording of events and measurements in the card log
  • Data and event logging in the nonvolatile memory
  • Card firmware update through the network
  • 10/100 Mb Ethernet (RJ-45 connector) with auto-negotiation
  • Measurement of humidity and temperature with the optional Environmental Monitoring Probe (EMP)
  • Easy installation (can be installed while the UPS is online, which maintains the highest availability)

An optional EMP (part number 46M4113) is used to report local temperature and humidity values and make that information available to management tools. The EMP connects to the UPS via the NMC.

Environmental Monitoring Probe (EMP)

Figure 3. Environmental Monitoring Probe

The EMP has the following features:

  • Monitors temperature, humidity, and status of two user-provided contact devices/sensors
  • Connects to an NMC through an RJ-45 CAT5 Ethernet cable (1 m cable included with the EMP)
  • Can be located up to 20 m (65.6 ft) from the UPS
  • Measures ambient temperatures between 0 - 80 °C (32 - 176 °F) with an accuracy of ±1 °C
  • Measures relative humidity between 10 - 90% with an accuracy of ±5%
  • Temperature, humidity, and contact closure status can be displayed through a web browser
  • Supports user-defined alarm thresholds for temperature, humidity, and contact closure status
  • Events are stored in the NMC's event log
  • Sends SNMP alarms to network management systems
  • Sends e-mail notifications through SMTP

Features

A UPS is a device that acts as a defensive barrier between electronic equipment and incoming power problems. It conditions, regulates, and filters out power disturbances to ensure a clean power source for IT equipment. A UPS also provides battery backup if there is a power failure.

In today’s high availability server environments, unplanned power outages or line quality irregularities can have a considerable financial impact on all sized businesses. The typical utility power is 99.9% available, but that means that there can be almost 9 hours of downtime a year, not to mention brownouts and other power quality problems. Selecting the right UPS can help protect against these potentially costly incidents.

The RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower UPS units are most effective against power failures, power sags, power surges, under-voltage, and over-voltage.

The RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower UPS models offer the following features:

  • High-efficiency protection for more real power (Watts) in a compact tower or 2U rack design, which lowers power and cooling consumption
  • A graphical Liquid Crystal Display (LCD) that provides intuitive configuration, management, and monitoring capabilities in the following languages to reduce management complexity:
    • English
    • French
    • German
    • Spanish
    • Russian
    • Portuguese
    • Italian
  • Hot-swappable batteries for maximum uptime, availability, and ease of maintenance
  • Standard UPS Power Manager software that provides effective local or remote power monitoring and management for servers and virtual machines, and allows for graceful remote system shutdown
  • ABM technology that significantly extends battery service life and optimizes recharge time
  • Load segments for individual control of receptacle groups to manage sequential shut downs and start ups and reserve battery run time for the most critical equipment
  • Optional external battery modules (EBMs) that provide extra run time to critical systems during a prolonged power outage
  • An optional NMC for enhanced UPS monitoring and control over-the-network through a standard web browser
  • An optional EMP for thermal management requirements (temperature and humidity)
  • Dual channel communication through the USB or RS-232 port and an optional NMC at the same time to maximize communications flexibility
  • The USB port supports HID (Human Interface Device) Power Device Class which means that the UPS can be directly managed by operating systems that support such USB classes.
  • Remote flash upgradeable firmware for the UPS and NMC, which makes it an ideal solution for remote locations
  • An ROO/RPO port to control power of the UPS unit through a wired remote switch

Technical specifications

Table 4 lists the technical specifications for the 100-125 V UPS models.

Table 3. Technical specifications for 100-125 V models
Specification RT1.5kVA 2U Rack or Tower UPS (100-125VAC) RT2.2kVA 2U Rack or Tower UPS (100-125VAC) RT3kVA 2U Rack or Tower UPS (100-125VAC)
General
Part number 55941AX 55942AX 55943AX
Form factor 2U Rack or Tower 2U Rack or Tower 2U Rack or Tower
Topology Line interactive, high frequency, sinewave output
VA/Watts rating 1440 VA/1440 W @ 120 V 1950 VA/1920 W 3000 VA/2700 W
Efficiency (on utility power) Up to 98% Up to 99% Up to 99%
Energy Star compliant Yes Yes Yes
Electrical input
Input voltage 100 - 125 V AC 100 - 125 V AC 100 - 125 V AC
Input frequency 50/60 Hz 50/60 Hz 50/60 Hz
Max input amperage 12 A 16 A 24 A
Input connector NEMA 5-15P (12 A) NEMA 5-20P (16 A) NEMA L5-30P (24 A)
Input line cord Fixed 2.5 m (8 ft) NEMA 5-15P Fixed 2.5 m (8 ft) NEMA 5-20P Fixed 2.5 m (8 ft) NEMA L5-30P
Electrical output
Output voltage settings 100/120/125 V AC 100/120/125 V AC 100/120/125 V AC
Output frequency 50/60 Hz 50/60 Hz 50/60 Hz
Output power capacity
  • 100 V AC: 1200 VA/1200 W
  • 120-125 V AC: 1440 VA/1440 W
  • 100 V AC: 1330 VA/1300 W
  • 120-125 V AC: 1950 VA/1920 W
  • 100 V AC: 2400 VA/2160 W
  • 120-125 V AC: 3000 VA/2700 W
Output connectors
  • 8x NEMA 5-15R (12 A)
  • 8x NEMA 5-20R (16 A)
  • 6x NEMA 5-20R (16 A)
  • 1x NEMA L5-30R (24 A)
Output load segments
  • Master: 4x 5-15R
  • Group 1: 2x 5-15R
  • Group 2: 2x 5-15R
  • Master: 4x 5-20R
  • Group 1: 2x 5-20R
  • Group 2: 2x 5-20R
  • Master: 2x 5-20R, 1x L5-30R
  • Group 1: 2x 5-20R
  • Group 2: 2x 5-20R
Batteries
Battery type Valve Regulated Lead Acid (VRLA): Maintenance-free, sealed, leak-proof
Battery capacity 7.2 Ah 9 Ah 9 Ah
Battery management ABM technology or temperature-compensated charging method (user selectable), automatic battery test and deep discharge protection, automatic recognition of external battery units
Battery replacement Hot-swap internal battery and extended battery modules
External battery support Up to 4 (PN 55942BX) Up to 4 (PN 55942BX) Up to 4 (PN 55943BX)
Typical backup times See Table 6
Communications and management
USB port (Type B) Yes Yes Yes
RS-232 serial port (RJ-45) Yes Yes Yes
10/100 Mbps Ethernet port (RJ-45) Optional with Network Management Card, 46M4110
Environmental monitoring Optional with Environmental Monitoring Probe, 46M4113 (requires Network Management Card, 46M4110)
Management software UPS Power Manager (UPM) and UPS Power Protector (UPP)
Control panel Intelligent 5-button graphical LCD
LED indicators Power On, On Battery, and Alarm
Remote On/Off and Power Off Remote On/Off (ROO) and Remote Power Off (RPO) terminal block connector

The following table lists the technical specifications for the 2U Rack or Tower 200-240 V UPS models.

Table 4. Technical specifications for 200-240 V models
Specification RT1.5kVA 2U Rack or Tower UPS (200-240VAC) RT2.2kVA 2U Rack or Tower UPS (200-240VAC) RT3kVA 2U Rack or Tower UPS (200-240VAC)
General
Part number 55941KX 55942KX 55943KX
Form factor 2U Rack or Tower 2U Rack or Tower 2U Rack or Tower
Topology Line interactive, high frequency, sinewave output
VA/Watts rating 1500 VA/1100 W 2200 VA/1980 W 3000 VA/2700 W
Efficiency (on utility power) Up to 98% Up to 99% Up to 99%
Energy Star compliant Yes Yes Yes
Electrical input
Input voltage 200 - 240 V AC 200 - 240 V AC 200 - 240 V AC
Input frequency 50/60 Hz 50/60 Hz 50/60 Hz
Max input amperage 10 A 16 A 16 A
Input connector IEC 320 C14 (10 A) IEC 320 C20 (16 A) IEC 320 C20 (16 A)
Input line cord Optional (See Table 2) Optional (See Table 3) Optional (See Table 3)
Electrical output
Output voltage settings 200/208/220/230/240 V AC 200/208/220/230/240 V AC 200/208/220/230/240 V AC
Output frequency 50/60 Hz 50/60 Hz 50/60 Hz
Output power capacity 200-240 V AC: 1550 VA / 1100 W
  • 200 V AC: 1700 VA/1530 W
  • 208 V AC: 1980 VA/1780 W
  • 220-240 V AC: 2200 VA/1980 W
  • 200 V AC: 2700 VA/2430 W
  • 208-240 V AC: 3000 VA/2700 W
Output connectors 8x IEC 320 C13 (10 A)
  • 8x IEC 320 C13 (10 A)
  • 1x IEC 320 C19 (16 A)
  • 8x IEC 320 C13 (10 A)
  • 1x IEC 320 C19 (16 A)
Output load segments
  • Master: 4x C13
  • Group 1: 2x C13
  • Group 2: 2x C13
  • Master: 4x C13, 1x C19
  • Group 1: 2x C13
  • Group 2: 2x C13
  • Master: 4x C13, 1x C19
  • Group 1: 2x C13
  • Group 2: 2x C13
Batteries
Battery type Valve Regulated Lead Acid (VRLA): Maintenance-free, sealed, leak-proof
Battery capacity 7.2 Ah 9 Ah 9 Ah
Battery management ABM technology or temperature-compensated charging method (user selectable), automatic battery test and deep discharge protection, automatic recognition of external battery units
Battery replacement Hot-swap internal battery and extended battery modules
External battery support Up to 4 (PN 55942BX) Up to 4 (PN 55942BX) Up to 4 (PN 55943BX)
Typical backup times See Table 7
Communications and management
USB port (Type B) Yes Yes Yes
RS-232 serial port (RJ-45) Yes Yes Yes
10/100 Mbps Ethernet port (RJ-45) Optional with the Network Management Card, 46M4110 Yes (on the NMC)
Environmental monitoring Optional with the Environmental Monitoring Probe, 46M4113 (requires the Network Management Card, 46M4110)
Management software UPS Power Manager (UPM) and UPS Power Protector (UPP)
Control panel Intelligent 5-button graphical LCD
LED indicators Power On, On Battery, and Alarm
Remote On/Off and Power Off Remote On/Off (ROO) and Remote Power Off (RPO) terminal block connector

The following two tables list the expected period that the 2U Rack or Tower UPS models operate based only on batteries, depending on the load.

Note: Battery backup times are approximate and can vary with equipment, configuration, battery age, and temperature.

Table 5. 2U Rack or Tower 100-125 V UPS runtime chart
Load
Run time, Minutes
Percentage Watts No EBM 1x EBM 2x EBMs 3x EBMs 4x EBMs
RT1.5kVA 2U Rack or Tower UPS (100-125VAC)
20% 288 W 39 171 288 405 523
30% 432 W 23 109 188 266 344
40% 576 W 16 77 134 191 248
50% 720 W 11 54 97 140 183
60% 864 W 7 45 82 119 155
70% 1008 W 6 37 69 101 133
80% 1152 W 5 31 58 86 113
90% 1296 W 4 25 49 72 96
100% 1440 W 3 21 41 62 82
RT2.2kVA 2U Rack or Tower UPS (100-125VAC)
20% 384 W 35 137 242 346 451
30% 576 W 21 83 150 218 286
40% 768 W 13 57 106 155 203
50% 960 W 9 40 75 109 143
60% 1152 W 6 32 59 82 114
70% 1344 W 5 27 49 66 94
80% 1536 W 4 22 40 53 78
90% 1728 W 3 18 34 43 65
100% 1920 W 3 15 29 36 57
RT3kVA 2U Rack or Tower UPS (100-125VAC)
10% 270 W 55 242 416 590 764
20% 540 W 30 144 247 349 452
30% 810 W 18 87 151 214 277
40% 1080 W 13 61 107 153 199
50% 1350 W 10 41 74 107 140
60% 1620 W 8 35 64 92 121
70% 1890 W 7 29 54 78 103
80% 2160 W 5 25 46 67 88
90% 2430 W 4 22 40 58 77
100% 2700 W 4 19 35 52 68
Table 6. 2U Rack or Tower 200-240 V UPS runtime chart
Load
Run time, Minutes
Percentage Watts No EBM 1x EBM 2x EBMs 3x EBMs 4x EBMs
RT1.5kVA 2U Rack or Tower UPS (200-240VAC)
20% 270 W 30 158 267 375 483
30% 405 W 20 105 197 289 380
40% 540 W 14 77 150 223 296
50% 675 W 10 74 125 176 227
60% 810 W 8 61 104 146 189
70% 945 W 7 48 82 117 151
80% 1080 W 5 38 68 97 127
90% 1215 W 4 32 60 88 116
100% 1350 W 3 25 52 78 105
RT2.2kVA 2U Rack or Tower UPS (200-240VAC)
20% 396 W 29 101 181 261 341
30% 594 W 16 66 124 182 240
40% 792 W 10 49 91 132 173
50% 990 W 7 35 66 97 128
60% 1188 W 6 30 56 81 106
70% 1386 W 4 25 45 65 84
80% 1584 W 3 21 38 54 70
90% 1782 W 2 19 34 49 64
100% 1980 W 2 17 30 44 58
RT3kVA 2U Rack or Tower UPS (200-240VAC)
10% 270 W 65 240 437 636 833
20% 540 W 33 128 223 320 416
30% 810 W 21 84 152 218 285
40% 1080 W 14 59 108 157 205
50% 1350 W 10 44 80 116 152
60% 1620 W 8 37 69 100 131
70% 1890 W 5 31 57 83 110
80% 2160 W 4 26 49 72 95
90% 2430 W 3 23 45 66 87
100% 2700 W 3 21 40 60 79

Leak current: Important specifications on UPS leak current and circuit breaker recommendations can be found in Support Tip HT511959, https://datacentersupport.lenovo.com/solutions/HT511959.

Connectors and controls

The front of the 2U Rack or Tower UPS units feature a 5-button graphical LCD. The display provides useful information about the UPS, load status, events, measurements, and settings.

The following figure shows the control panel on the front of the 2U Rack or Tower UPS.

Control panel on the front of the 2U Rack or Tower UPS
Figure 4. Control panel on the front of the 2U Rack or Tower UPS

The following functions are available on the control panel:

  • Status information: Displays the battery status, load percentage, output power, operational mode, and load group information.
  • Measurements: Displays the output Watts VA, amperage, power factor, voltage, frequency, input voltage, input frequency, battery voltage, efficiency, and power usage.
  • Control: Displays the battery test, reset error state, configure load segments, clear power usage measurements, and restore settings.
  • Settings: Allows you to change product general parameters and set input and output parameters, on/off conditions, and battery configuration.
  • Fault log: Displays the event log and alarm history.
  • Identification: Displays the machine type, model, and serial number of the unit, and the firmware level of the UPS, including the optional NMC’s firmware level and IP address, if installed.

The following figure shows the rear view of the RT1.5kVA 2U Rack or Tower UPS (100-125VAC) (55941AX).

Rear view of the RT1.5kVA 2U Rack or Tower UPS (100-125VAC) (55941AX)
Figure 5. Rear view of the RT1.5kVA 2U Rack or Tower UPS (100-125VAC) (55941AX)

The following figure shows the rear view of the RT2.2kVA 2U Rack or Tower UPS (100-125VAC) (55942AX).

Rear view of the RT2.2kVA 2U Rack or Tower UPS (100-125VAC) (55942AX)
Figure 6. Rear view of the RT2.2kVA 2U Rack or Tower UPS (100-125VAC) (55942AX)

The following figure shows the rear view of the RT3kVA 2U Rack or Tower UPS (100-125VAC) (55943AX).

Rear view of the RT3kVA 2U Rack or Tower UPS (100-125VAC) (55943AX)
Figure 7. Rear view of the RT3kVA 2U Rack or Tower UPS (100-125VAC) (55943AX)

The following figure shows the rear view of the RT1.5kVA 2U Rack or Tower UPS (200-240VAC) (55941KX).

Rear view of the RT1.5kVA 2U Rack or Tower UPS (200-240VAC) (55941KX)
Figure 8. Rear view of the RT1.5kVA 2U Rack or Tower UPS (200-240VAC) (55941KX)

The following figure shows the rear view of the RT2.2kVA 2U Rack or Tower UPS (200-240VAC) (55942KX).

Rear view of the RT2.2kVA 2U Rack or Tower UPS (200-240VAC) (55942KX)
Figure 9. Rear view of the RT2.2kVA 2U Rack or Tower UPS (200-240VAC) (55942KX)

The following figure shows the rear view of the RT3kVA 2U Rack or Tower UPS (200-240VAC) (55943KX).

Rear view of the RT3kVA 2U Rack or Tower UPS (200-240VAC) (55943KX)
Figure 10. Rear view of the RT3kVA 2U Rack or Tower UPS (200-240VAC) (55943KX)

The following figure shows the rear view of the 1.5kVA/2.2kVA (top) and 3kVA (bottom) 2U Rack or Tower Extended Battery Modules.

Rear view of the 1.5kVA/2.2kVA (top) and 3kVA (bottom) 2U Rack or Tower Extended Battery Modules
Figure 11. Rear view of the 1.5kVA/2.2kVA (top) and 3kVA (bottom) 2U Rack or Tower Extended Battery Modules

Physical specifications

The 2U Rack or Tower UPS units have the following physical specifications (approximate):

  • Height: 86 mm (3.4 in.)
  • Width: 441 mm (17.4 in.)
  • Depth:
    • RT1.5kVA and RT2.2kVA: 522 mm (20.6 in.)
    • RT3kVA: 647 mm (25.5 in.)
  • Weight:
    • RT1.5kVA (100-125VAC): 29.4 kg (64.7 lb)
    • RT2.2kVA (100-125VAC): 29.6 kg (65.3 lb)
    • RT3kVA (100-125VAC): 39.5 kg (87.2 lb)
    • RT1.5kVA (200-240VAC): 27.6 kg (60.9 lb)
    • RT2.2kVA (200-240VAC): 28.5 kg (62.8 lb)
    • RT3kVA (200-240VAC): 38.1 kg (84.0 lb)

The 2U Rack or Tower Extended Battery Modules have the following physical specifications (approximate):

  • Height: 86 mm (3.4 in.)
  • Width: 441 mm (17.4 in.)
  • Depth:
    • RT1.5kVA/RT2.2kVA: 522 mm (20.6 in.)
    • RT3kVA: 647 mm (25.5 in.)
  • Weight:
    • RT1.5kVA/RT2.2kVA: 32.8 kg (72.3 lb)
    • RT3kVA: 46.4 kg (102.3 lb)

Operating environment

The 2U Rack or Tower UPS units are supported in the following environment:

  • Temperature (operation): 0 - 40 °C (32 - 104 °F)
  • Relative humidity: 20 - 90%
  • Maximum altitude (operation): 3,000 m (9,843 ft)

Note: These UPS units are not supported in a maritime environment.

Agency approvals

The 2U Rack or Tower UPS units conform to the following regulations:

  • FCC
  • UL
  • CSA or cUL
  • CE Mark
  • NOM
  • GOST
  • BSMI Taiwan
  • CB Report
  • VCCI
  • C-Tick (Australia)
  • IRAM (Argentina)

Warranty

The 2U Rack or Tower UPS models and the Extended Battery Module (EBM), including batteries, have a 3-year limited warranty. Optional features have a 1-year warranty.

Management software

Optional software can be downloaded to be used the UPS units. This software is the UPS Power Manager (UPM) and UPS Power Protector (UPP) software. The UPM software can manage multiple devices. The UPP software is used to manage a single device. Note that a device refers to a UPS or a PDU.

Tip: The UPS offers a USB port that supports the HID (Human Interface Device) Power Device Class that enables the UPS to be locally managed directly by the operating system of the attached server.

UPS Power Manager

The UPS Power Manager (UPM) software is free to use for up to 10 devices (PDUs or UPS units). It is available either as a Windows application or a virtual appliance (OVF file). Download the software from:
https://datacentersupport.lenovo.com/us/en/solutions/lnvo-ups-mgmt

For up to 100 devices, a Silver license can be purchased. For up to 600 devices, a Gold license can be purchased. The following table shows the part number ordering information for each version of the UPM software.

Table 7. UPM part numbers
Part Number Feature Code Description
None None Basic (free) UPM software (1-10 devices can be managed)
00YE464 ATS2 Silver key license (up to 100 devices can be managed)
00YE465 ATS3 Gold key license (up to 600 devices can be managed)

The purchase of a Silver or Gold license adds additional management features not found in the Basic license. The following table shows the UPM licenses and features for each license when managing Lenovo UPS units.

Table 8. Comparison of UPM features
Features of UPM Basic License (free) Silver License Gold License
Number of devices (UPS or PDU) Up to 10 Up to 100 Up to 500
Identify and monitor third-party power devices Yes Yes Yes
Shut down server and host without crashing Yes Yes Yes
Configuration Policy Yes Yes Yes
Control rack PDUs (on, off and reboot sections or outlets) (1) Yes Yes Yes
Plug-in for VMware vCenter Yes Yes Yes
Enter and exit maintenance mode Yes Yes Yes
Shutdown Virtual Hosts (e.g. VMware ESXi) Yes Yes Yes
Shutdown Storage Yes Yes Yes
Advanced Event Action with Standard Events No Yes Yes
Miscellaneous Advanced Actions, Generic SSH action No Yes Yes
Shut down specific, targeted virtual machines No Yes Yes
Migrate virtual machines to targeted hosts No Yes Yes
Virtual machines load shedding No Yes Yes
Trigger targeted, automatic advanced actions No Yes Yes
Safely shut down and restore high availability environments No Yes Yes
Fully virtualized cluster shutdown No Yes Yes
Integrated with Microsoft Hyper-V virtualization platform to facilitate guest virtual machine shutdown or suspend, and graceful shutdown of the Hyper-V hypervisor No Yes Yes
Integrated with VMware vSAN hyperconverged infrastructure software to enable graceful shutdown of logical data layer used by vSAN and full vSAN clusters No Yes Yes
Integrated with Nutanix Acropolis Hypervisor to gracefully shut down of user VMs, controller VMs then AHV on Lenovo HX appliances running AHV No Yes (2) Yes
Manage third-party power devices No No Yes
OpenStack monitoring and control No No Yes

(1) Support for SNMPv1 required at target device
(2) Requires UPM v1.65.221 or higher

UPM brings managing various power and environmental devices under control through a single, web-based interface. The UPM software solution ensures system uptime and data integrity by allowing you to monitor, manage, and control the devices on your network remotely.

The UPM user interface is shown in the following figure.

UPS Power Manager user interface
Figure 12. UPM User Interface

The UPM software offers the following features:

  • Monitors and manages multiple power and environmental devices from a web browser or your virtual machine management dashboard
  • Seamlessly integrates into popular virtualization infrastructures, including VMware ESXi, Microsoft Hyper-V, Citrix XenServer, and Linux KVM
  • Triggers live migration for virtual machines during power outages
  • By using a user-definable tree structure, enables grouping, access, and management of multiple devices across multiple locations
  • Monitors power consumption, which helps track ways to improve energy efficiency
  • Uses auto discovery to provide fast installation by automatically detecting devices on the network
  • Mass-upgrades firmware, which reduces network management card setup and maintenance time

UPS Power Protector

The UPP software is free to download and use. Download it from the following links (v1.52.007):

UPP software facilitates automatic, graceful shutdown of computers, servers, and network devices that are powered by a UPS, which saves all work-in-progress and ensures data integrity. UPP's user interface provides detailed information about connected servers and UPS units through USB and serial or network communication.

The UPP user interface is shown in the following figure.

UPS Power Protector user interface
Figure 13. UPP User Interface

The UPP software offers the following features:

  • Helps avoid data loss by gracefully shutting down computers and virtual machines or servers that are powered by a UPS during an extended power outage
  • Keeps servers running smoothly by automatically identifying hang-ups and rebooting the machine by using a watchdog capability
  • Provides redundancy capability for dual-cord servers
  • An easy-to-use web browser interface
  • Communicates with the protected device directly (via USB or serial) or through the network (via NMC)

Supported servers

The 2U Rack or Tower UPS offerings are compatible with all ThinkSystem, System x and ThinkServer systems and other devices that require AC power.

To determine the best fit UPS for a particular configuration, the following needs to be considered:

  • Total power load of the hardware that will be connected to the UPS
  • Number and type of outlets required
  • UPS outlet and group limitations for connecting the hardware to the UPS

To determine chassis, node and server overall power capacities, use the Power Configurator tool. The tool can be downloaded from http://support.lenovo.com/documents/LNVO-PWRCONF

To determine the power draw of other devices such as storage and switching that will be attached to the UPS, refer to the products user manual for the maximum power draw. 

For additional technical information on the UPS line cords, outlets and grouping refer to the UPS Technical Reference, https://support.lenovo.com/docs/UM104477

Supported rack cabinets

The 2U Rack or Tower UPS units can be installed in the compatible rack cabinets as listed in Table 8.

Table 9. Rack cabinets

Part number Description
201886X 11U Office Enablement Kit
93072RX 25U Standard Rack
93072PX 25U Static S2 Standard Rack
93634PX 42U 1100mm Dynamic Rack
93634EX 42U 1100mm Dynamic Expansion Rack
93604PX 42U 1200mm Deep Dynamic Rack
93604EX 42U 1200mm Deep Dynamic Expansion Rack
93614PX 42U 1200mm Deep Static Rack
93614EX 42U 1200mm Deep Static Expansion Rack
93084PX 42U Enterprise Rack
93084EX 42U Enterprise Expansion Rack
93074RX 42U Standard Rack
93074XX 42U Standard Rack Extension
93624PX 47U 1200mm Deep Static Rack
93624EX 47U 1200mm Deep Static Expansion Rack
93634AX PureFlex® System 42U Rack
93634BX PureFlex System 42U Expansion Rack
93634CX PureFlex System 42U Rack
93634DX PureFlex System 42U Expansion Rack

Related product families

Product families related to this document are the following:

Trademarks

Lenovo and the Lenovo logo are trademarks or registered trademarks of Lenovo in the United States, other countries, or both. A current list of Lenovo trademarks is available on the Web at https://www.lenovo.com/us/en/legal/copytrade/.

The following terms are trademarks of Lenovo in the United States, other countries, or both:
Lenovo®
System x®
ThinkServer®
ThinkSystem®

The following terms are trademarks of other companies:

Linux® is the trademark of Linus Torvalds in the U.S. and other countries.

Microsoft®, Hyper-V®, and Windows® are trademarks of Microsoft Corporation in the United States, other countries, or both.

Other company, product, or service names may be trademarks or service marks of others.