skip to main content

T1kVA and T1.5kVA Tower Uninterruptible Power Supplies

Product Guide (withdrawn product)

Home
Top
Updated
15 Mar 2024
Form Number
TIPS1230
PDF size
20 pages, 772 KB

Abstract

The T1kVA and T1.5kVA Tower Uninterruptible Power Supply (UPS) offerings provide power protection with increased efficiency and simplified power management to safeguard the high-availability of Lenovo server environments. With efficiency ratings of up to 97%, these compact tower designs can help reduce energy usage without compromising performance or reliability.

Withdrawn: All UPS models described in this product guide are now withdrawn from marketing.

Change History

Changes in the March 15, 2024 update:

  • The T1.5kVA Tower UPS units are withdrawn from marketing

Introduction

The T1kVA and T1.5kVA Tower Uninterruptible Power Supply (UPS) offerings provide power protection with increased efficiency and simplified power management to safeguard the high-availability of Lenovo server environments. With efficiency ratings of up to 97%, these compact tower designs can help reduce energy usage without compromising performance or reliability.

ower UPS unit (T1kVA or T1.5kVA)
Figure 1. Tower UPS unit (T1kVA or T1.5kVA)

Did you know?

T1kVA and T1.5kVA Tower UPS units feature Advanced Battery Management (ABM) technology that uses a unique three-stage charging technique that significantly extends battery service life and optimizes recharge time, compared to traditional charging.

T1kVA and T1.5kVA Tower UPS units can enhance system availability with individual receptacle groups or load segments that can be programmed and controlled, which allows mission-critical devices to be prioritized during shutdown to preserve battery run time if there is a prolonged power outage.

T1kVA and T1.5kVA Tower UPS units come standard with UPS Power Manager (UPM) power management software that integrates seamlessly with the major virtual platforms, which enables you to view and manage your entire power system from your current dashboard. It also triggers live migration during power outages and avoids data loss by gracefully shutting down virtual machines and hosts in a cluster if there is an extended power outage.

Ordering information

Table 1 shows the part numbers and feature codes for the T1kVA and T1.5kVA Tower UPS models and options.

Withdrawn: All UPS models listed below are now withdrawn from marketing.

Table 1. Ordering part numbers and feature codes

Part number Feature code Description
UPS units
55951AX A548 (5595-TU1) T1kVA Tower UPS (100-125VAC)
55951KX A549 (5595-TU1) T1kVA Tower UPS (200-240VAC)
55952AX A54A (5595-TU2) T1.5kVA Tower UPS (100-125VAC)
55952KX A54C (5595-TU2) T1.5kVA Tower UPS (200-240VAC)
Options
46M4110 6145 UPS Network Management Card
46M4113 6146 Environmental Monitoring Probe

The UPS models ship the following items:

  • An accessory kit, which contains the following items:
    • Serial cable: 1.2 m (4 ft)
    • USB cable
    • Remote emergency power-off (REPO) connector
  • A documentation kit, which contains the following items:
    • Documentation package
    • Software CD, which contains UPM software

The 100 - 125 V models (1AX and 2AX) ship with fixed 1.8 m NEMA 5-15P line cord. The 200 - 240 V models (1KX and 2KX) do not ship with line cords. Table 2 lists the compatible line cords, which are suitable for models 1KX and 2KX.

Table 2. Line cords for 200 - 240 V models (models 1KX and 2KX)
Description Part number Feature code
10A/250V C13 to NEMA 6-15P 2.8m line cord 46M2592 A1RF
Argentina 10A line C13 to IRAM 2063 (2.8M) 39Y7930 6222
Australia/NZ 10A line C13 to SAA-AS C112 (2.8M) 39Y7924 6211
Brazil 10A line C13 to NBR 6147 (2.8M) 39Y7929 6223
China 6A line C13 to GB 2099.1 (2.8M) 39Y7928 6210
Denmark 10A line C13 to DK2-5A (2.8M) 39Y7918 6213
European 10A line C13 to CEE 7/7 (2.8M) 39Y7917 6212
India 6A line C13 to Fig 68 (2.8M) 39Y7927 6269
Israel 10A line C13 to SI 32 (2.8M) 39Y7920 6218
Italy 10A line C13 to CEE 7/7 (2.8M) 39Y7921 6217
Japan 10A line C13 to JIS C-8303 (2.8M) 46M2593 A1RE
Korea 7A line C13 to KETI 15A/250V (2.8M) 39Y7925 6219
South Africa 10A line C13 to SABS 164/1 (2.8M) 39Y7922 6214
Switzerland 10A line C13 to SEV 1011 (2.8M) 39Y7919 6216
Taiwan 10A/250V C13/CNS 10917 2.8m line cord 81Y2375 A0RF
United Kingdom 10A line C13 to BS 1363 (2.8M) 39Y7923 6215

The T1kVA and T1.5kVA Tower UPS models also come equipped with a communication bay for the installation of an optional Network Management Card (46M4110). The Network Management Card (NMC) provides convenient, over-the-network UPS remote monitoring and management through a standard web browser or UPM software. The following figure shows the UPS NMC.

UPS Network Management Card (NMC)

Figure 2. UPS Network Management Card

The NMC has the following features:

  • Versatile connectivity through HTTP, SNMP, SMTP, Telnet, SSL, and SSH
  • Simultaneous shutdown of protected servers
  • Configuration of automatic email messages in response to UPS alarms and to transmit periodic reports
  • Customizable actions, including automatic shutdown if there is an extended power failure with standard UPS Power Protector software
  • Control of UPS on/off switching with a web browser
  • Adjustment and control of load segments through the HTML interface, including sequential starting of the installation and optimization of backup time by shutting down non-priority systems
  • Automatic date and time adjustment through an NTP server
  • Dual stack IP v4/IP v6
  • Recording of events and measurements in the card log
  • Data and event logging in the nonvolatile memory
  • Card firmware update through the network
  • 10/100 Mb Ethernet (RJ-45 connector) with auto-negotiation
  • Measurement of humidity and temperature with the optional Environmental Monitoring Probe (EMP)
  • Easy installation (can be installed while the UPS is online to maintain the highest system availability)

An optional EMP (part number 46M4113) is used to report local temperature and humidity values and make that information available to management tools. The EMP connects to the UPS via the NMC. The EMP is shown in the following figure.

Environmental Monitoring Probe (EMP)

Figure 3. Environmental Monitoring Probe

The EMP has the following features:

  • Monitors temperature, humidity, and status of two user-provided contact devices or sensors
  • Connects to an NMC through an RJ-45 CAT5 Ethernet cable (1 m cable included with the EMP)
  • Can be located up to 20 m (65.6 ft) from the UPS
  • Measures ambient temperatures 0 - 80 °C (32 - 176 °F) with an accuracy of ±1 °C
  • Measures relative humidity 10 - 90% with an accuracy of ±5%
  • Displays temperature, humidity, and contact closure status through a web browser
  • Supports user-defined alarm thresholds for temperature, humidity, and contact closure status
  • Stores events in the NMC's event log
  • Sends SNMP alarms to network management systems
  • Sends e-mail notifications through SMTP

Features

A UPS is a device that acts as a defensive barrier between electronic equipment and incoming power problems. It conditions, regulates, and filters out power disturbances to ensure a clean power source for IT equipment. A UPS also provides battery backup if there is a power failure.

In today’s high availability server environments, unplanned power outages or line quality irregularities can have a considerable financial effect on all sized businesses. The typical utility power is 99.9% available, but that means that there can be almost 9 hours of downtime a year, which includes brownouts and other power quality problems.

Selecting the right UPS can help protect against these potentially costly incidents.

The T1kVA and T1.5kVA Tower UPS units are most effective against five power problems: power failures, power sags, power surges, under-voltage, and over-voltage.

The T1kVA and T1.5kVA Tower UPS models offer the following features:

  • High-efficiency protection delivers more real power (watts) in a compact design, lowering power, and cooling consumption
  • Graphical Liquid Crystal Display (LCD) provides intuitive configuration, management, and monitoring capabilities in the following languages to reduce management complexity:
    • English
    • French
    • German
    • Spanish
    • Russian
    • Portuguese
    • Italian
  • Hot-swappable batteries for maximum uptime, availability, and ease of maintenance
  • Standard UPS Power Manager software provides effective local or remote power monitoring and management for servers and virtual machines and allows for graceful remote system shutdown
  • ABM technology significantly extends battery service life and optimizes recharge time
  • Load segments for individual control of receptacle groups to manage sequential shut downs and start ups and reserve battery run time for the most critical equipment
  • Optional NMC for enhanced UPS monitoring and control over-the-network through a standard web browser
  • Optional Environmental Monitoring Probe for thermal management requirements (temperature and humidity)
  • Allows dual channel communication through the USB or RS-232 port and an optional NMC at the same time to maximize communications flexibility
  • Remote flash upgradeable firmware for the UPS and NMC, which makes it an ideal solution for remote locations
  • Includes a Remote On/Off (ROO)/Remote Power Off (RPO) port to control power of the UPS unit through a wired remote switch

Technical specifications

Table 3 lists the technical specifications for the T1kVA and T1.5kVA Tower UPS units.

Withdrawn: The T1kVA UPS units are withdrawn from marketing

Table 3. Technical specifications
Specification T1kVA Tower UPS (100-125VAC) T1kVA Tower UPS (200-240VAC) T1.5kVA Tower UPS (100-125VAC) T1.5kVA Tower UPS (200-240VAC)
General
Part number 55951AX 55951KX 55952AX 55952KX
Form factor Tower Tower Tower Tower
Topology Line interactive, high frequency, sinewave output
VA/Watts rating 1000 VA/770 W 1150 VA/770 W 1440 VA/1100 W 1550 VA/1100 W
Efficiency (on utility power) Up to 97% Up to 97% Up to 97% Up to 97%
Energy Star compliant No Yes Yes Yes
Electrical input
Input voltage 100 - 125 V AC 200 - 240 V AC 100 - 125 V AC 200 - 240 V AC
Input frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Max input amperage 8.8 A 5.3 A 12 A 7.1 A
Input connector NEMA 5-15P (12 A) IEC 320 C14 (10 A) NEMA 5-15P (12 A) IEC 320 C14 (10 A)
Input line cord Fixed 1.8 m (6 ft) NEMA 5-15P Optional (See Table 3) Fixed 1.8 m (6 ft) NEMA 5-15P Optional (See Table 3)
Electrical output
Output voltage settings 100/120/125 V AC 200/208/220/230/240 V AC 100/120/125 V AC 200/208/220/230/240 V AC
Output frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Output power capacity
  • 100 V AC: 833 VA/641 W
  • 120 - 125 V AC: 1000 VA/770 W
  • 200 - 208 V AC: 1035 VA/693 W
  • 220 - 240 V AC: 1150 VA/770 W
  • 100 V AC: 1080 VA/825 W
  • 120 - 125 V AC: 1440 VA/1100 W
  • 200 - 208 V AC: 1395 VA/990 W
  • 220 - 240 V AC: 1550 VA/1100 W
Output connectors 8x NEMA 5-15R (12 A) 8x IEC 320 C13 (10 A) 8x NEMA 5-15R (12 A) 8x IEC 320 C13 (10 A)
Output load segments
  • Primary: 4x 5-15R
  • Group 1: 2x 5-15R
  • Group 2: 2x 5-15R
  • Primary: 4x C13
  • Group 1: 2x C13
  • Group 2: 2x C13
  • Primary: 4x 5-15R
  • Group 1: 2x 5-15R
  • Group 2: 2x 5-15R
  • Primary: 4x C13
  • Group 1: 2x C13
  • Group 2: 2x C13
Batteries
Battery type Valve Regulated Lead Acid (VRLA): Maintenance-free, sealed, and leak-proof
Battery capacity 9 Ah 9 Ah 9 Ah 9 Ah
Battery management ABM technology or temperature-compensated charging method (user selectable), automatic battery test, and deep discharge protection
Battery replacement Hot-swap internal battery
External battery support No No No No
Typical backup times See Table 5 See Table 6
Communications and management
USB port (Type B) Yes Yes Yes Yes
RS-232 serial port (RJ-45) Yes Yes Yes Yes
10/100 Mbps Ethernet port (RJ-45) Optional with Network Management Card, 46M4110
Environmental monitoring Optional with Environmental Monitoring Probe, 46M4113 (requires Network Management Card 46M4110)
Management software UPS Power Manager and UPS Power Protector
Control panel Intelligent 5-button graphical LCD
LED indicators Power On, On Battery, and Alarm
Remote On/Off and Power Off Remote On/Off (ROO) and Remote Power Off (RPO) terminal block connector

The following two tables list the expected period that the T1kVA and T1.5kVA Tower UPS models operate solely on batteries, depending on the load.

Table 4. T1kVA Tower UPS runtime chart
Load
Run time in minutes
Percentage Watts T1kVA Tower UPS (100-125VAC) T1kVA Tower UPS (200-240VAC)
20% 154 W 33 33
30% 231 W 21 21
40% 308 W 15 15
50% 385 W 12 11
60% 462 W 9 9
70% 539 W 8 7
80% 616 W 7 6
90% 693 W 6 5
100% 770 W 5 4
Table 5. T1.5kVA Tower UPS runtime chart
Load
Run time in minutes
Percentage Watts T1.5kVA Tower UPS (100-125VAC) T1.5kVA Tower UPS (200-240VAC)
20% 220 W 42 42
30% 330 W 25 25
40% 440 W 18 18
50% 550 W 13 13
60% 660 W 11 11
70% 770 W 8 8
80% 880 W 6 6
90% 990 W 5 5
100% 1100 W 4 4

Note: Battery backup times are approximate and can vary with equipment, configuration, battery age, and temperature.

Leak current: Important specifications on UPS leak current and circuit breaker recommendations can be found in Support Tip HT511959, https://datacentersupport.lenovo.com/solutions/HT511959.

Connectors and controls

The T1kVA and T1.5kVA Tower UPS units have a 5-button graphical LCD on the front. The LCD provides useful information about the UPS, load status, events, measurements, and settings.

The following figure shows the control panel on the front of the Tower UPS.

Control panel on the front of the Tower UPS
Figure 4. Control panel on the front of the Tower UPS

The following functions are available on the control panel:

  • Status information: Displays the battery status, load percentage, output power, operational mode, and load group information.
  • Measurements: Displays the output watts VA, amperage, power factor, voltage, frequency, input voltage, input frequency, battery voltage, efficiency, and power usage.
  • Control: Displays the battery test, reset error state, configure load segments, clear power usage measurements, and restore settings.
  • Settings: Allows you to change product general parameters and set input and output parameters, on/off conditions, and battery configuration.
  • Fault log: Displays the event log and alarm history.
  • Identification: Displays the machine type, model, and serial number of the unit and the firmware level of the UPS, including the optional NMC’s firmware level, and IP address, if installed.

The following figure shows the rear view of the T1kVA Tower UPS (100-125 VAC) (55951AX).

5.4B64.jpg
Figure 5. Rear view of the T1kVA Tower UPS (100-125VAC) (55951AX)

The following figure shows the rear view of the T1kVA Tower UPS (200-240VAC) (55951KX).

11.2B4A.jpg
Figure 6. Rear view of the T1kVA Tower UPS (200-240VAC) (55951KX)

The following figure shows the rear view of the T1.5kVA Tower UPS (100-125VAC) (55952AX).

16.4C80.jpg
Figure 7. Rear view of the T1.5kVA Tower UPS (100-125VAC) (55952AX)

The following figure shows the rear view of the T1.5kVA Tower UPS (200-240VAC) (55952KX).

22.2D80.jpg
Figure 8. Rear view of the T1.5kVA Tower UPS (200-240VAC) (55952KX)

Physical specifications

The T1kVA Tower UPS unit has the following physical specifications (approximate):

  • Height: 233 mm (9.1 in.)
  • Width: 150 mm (5.9 in.)
  • Depth: 345 mm (13.6 in.)
  • Weight: 11.5 kg (24.4 lb)

The T1.5kVA Tower UPS unit has the following physical specifications (approximate):

  • Height: 233 mm (9.1 in.)
  • Width: 150 mm (5.9 in.)
  • Depth: 445 mm (17.5 in.)
  • Weight: 16.2 kg (35.3 lb)

Operating environment

The T1kVA and T1.5kVA Tower UPS units are supported in the following environment:

  • Temperature (operation):
    • T1kVA Tower UPS: 0 - 35 °C (32 - 95 °F)
    • T1.5kVA Tower UPS: 0 - 40 °C (32 - 104 °F)
  • Relative humidity: 5 - 95%
  • Maximum altitude (operation): 3,000 m (9,843 ft)

Note: These UPS units are not supported in a maritime environment.

Agency approvals

The T1kVA and T1.5kVA Tower UPS units conform to the following regulations:

  • FCC
  • UL
  • CSA or cUL
  • CE Mark
  • NOM
  • GOST
  • BSMI Taiwan
  • CB Report
  • VCCI
  • C-Tick (Australia)
  • IRAM (Argentina)

Warranty

The T1kVA and T1.5kVA Tower UPS, including batteries, have a three-year limited warranty. Optional features include a one-year warranty.

Management software

Optional software can be downloaded to be used the UPS units. This software is the UPS Power Manager (UPM) and UPS Power Protector (UPP) software. The UPM software can manage multiple devices. The UPP software is used to manage a single device. Note that a device refers to a UPS or a PDU.

UPS Power Manager

The UPS Power Manager (UPM) software is free to use for up to 10 devices (PDUs or UPS units). It is available either as a Windows application or a virtual appliance (OVF file). Download the software from:
https://datacentersupport.lenovo.com/us/en/solutions/lnvo-ups-mgmt

For up to 100 devices, a Silver license can be purchased. For up to 600 devices, a Gold license can be purchased. The following table shows the part number ordering information for each version of the UPM software.

Table 6. UPM part numbers
Part Number Feature Code Description
None None Basic (free) UPM software (1-10 devices can be managed)
00YE464 ATS2 Silver key license (up to 100 devices can be managed)
00YE465 ATS3 Gold key license (up to 600 devices can be managed)

The purchase of a Silver or Gold license adds additional management features not found in the Basic license. The following table shows the UPM licenses and features for each license when managing Lenovo UPS units.

Withdrawn: The Gold license is withdrawn from marketing.

Table 7. Comparison of UPM features
Features of UPM Basic License (free) Silver License Gold License
Number of devices (UPS or PDU) Up to 10 Up to 100 Up to 500
Identify and monitor third-party power devices Yes Yes Yes
Shut down server and host without crashing Yes Yes Yes
Configuration Policy Yes Yes Yes
Control rack PDUs (on, off and reboot sections or outlets) (1) Yes Yes Yes
Plug-in for VMware vCenter Yes Yes Yes
Enter and exit maintenance mode Yes Yes Yes
Shutdown Virtual Hosts (e.g. VMware ESXi) Yes Yes Yes
Shutdown Storage Yes Yes Yes
Advanced Event Action with Standard Events No Yes Yes
Miscellaneous Advanced Actions, Generic SSH action No Yes Yes
Shut down specific, targeted virtual machines No Yes Yes
Migrate virtual machines to targeted hosts No Yes Yes
Virtual machines load shedding No Yes Yes
Trigger targeted, automatic advanced actions No Yes Yes
Safely shut down and restore high availability environments No Yes Yes
Fully virtualized cluster shutdown No Yes Yes
Integrated with Microsoft Hyper-V virtualization platform to facilitate guest virtual machine shutdown or suspend, and graceful shutdown of the Hyper-V hypervisor No Yes Yes
Integrated with VMware vSAN hyperconverged infrastructure software to enable graceful shutdown of logical data layer used by vSAN and full vSAN clusters No Yes Yes
Integrated with Nutanix Acropolis Hypervisor to gracefully shut down of user VMs, controller VMs then AHV on Lenovo HX appliances running AHV No Yes (2) Yes
Manage third-party power devices No No Yes
OpenStack monitoring and control No No Yes

(1) Support for SNMPv1 required at target device
(2) Requires UPM v1.65.221 or higher

UPM brings managing various power and environmental devices under control through a single, web-based interface. The UPM software solution ensures system uptime and data integrity by allowing you to monitor, manage, and control the devices on your network remotely.

The UPM user interface is shown in the following figure.

UPS Power Manager user interface
Figure 9. UPM User Interface

The UPM software offers the following features:

  • Monitors and manages multiple power and environmental devices from a web browser or your virtual machine management dashboard
  • Seamlessly integrates into popular virtualization infrastructures, including VMware ESXi, Microsoft Hyper-V, Citrix XenServer, and Linux KVM
  • Triggers live migration for virtual machines during power outages
  • By using a user-definable tree structure, enables grouping, access, and management of multiple devices across multiple locations
  • Monitors power consumption, which helps track ways to improve energy efficiency
  • Uses auto discovery to provide fast installation by automatically detecting devices on the network
  • Mass-upgrades firmware, which reduces network management card setup and maintenance time

UPS Power Protector

The UPP software is free to download and use. Download it from the following links (v1.52.007):

UPP software facilitates automatic, graceful shutdown of computers, servers, and network devices that are powered by a UPS, which saves all work-in-progress and ensures data integrity. UPP's user interface provides detailed information about connected servers and UPS units through USB and serial or network communication.

The UPP user interface is shown in the following figure.

UPS Power Protector user interface
Figure 10. UPP User Interface

The UPP software offers the following features:

  • Helps avoid data loss by gracefully shutting down computers and virtual machines or servers that are powered by a UPS during an extended power outage
  • Keeps servers running smoothly by automatically identifying hang-ups and rebooting the machine by using a watchdog capability
  • Provides redundancy capability for dual-cord servers
  • An easy-to-use web browser interface
  • Communicates with the protected device directly (via USB or serial) or through the network (via NMC)

Supported servers

The T1kVA and T1.5kVA Tower UPS offerings are compatible with all ThinkSystem, System x and ThinkServer systems and other devices that require AC power.

To determine the best fit UPS for a particular configuration, the following needs to be considered:

  • Total power load of the hardware that will be connected to the UPS
  • Number and type of outlets required
  • UPS outlet and group limitations for connecting the hardware to the UPS

To determine chassis, node and server overall power capacities, use the Power Configurator tool. The tool can be downloaded from http://support.lenovo.com/documents/LNVO-PWRCONF

To determine the power draw of other devices such as storage and switching that will be attached to the UPS, refer to the products user manual for the maximum power draw. 

For additional technical information on the UPS line cords, outlets and grouping refer to the UPS Technical Reference, https://support.lenovo.com/docs/UM104477

 

Related product families

Product families related to this document are the following:

Trademarks

Lenovo and the Lenovo logo are trademarks or registered trademarks of Lenovo in the United States, other countries, or both. A current list of Lenovo trademarks is available on the Web at https://www.lenovo.com/us/en/legal/copytrade/.

The following terms are trademarks of Lenovo in the United States, other countries, or both:
Lenovo®
System x®
ThinkServer®
ThinkSystem®

The following terms are trademarks of other companies:

Linux® is the trademark of Linus Torvalds in the U.S. and other countries.

Microsoft®, Hyper-V®, and Windows® are trademarks of Microsoft Corporation in the United States, other countries, or both.

Other company, product, or service names may be trademarks or service marks of others.